Core material | aluminum |
The placeholder | is missing |
The screen | is missing |
The armor | is missing |
operating temperature – from -50 to +50 °C;
gasket temperature-not less than -20 °C;
permissible heating temperature of conductive cores, °C:
in normal operation — 90
in overload mode (up to 8 hours a day) – 130
short circuit with a short-circuit current flow of up to 5 seconds — 250
breaking strength of the carrier cable, kN, not less:
with a cable cross-section of 25 mm22 — 7,4;
with a cable cross-section of 35 mm22 — 10,3;
with a cable cross-section of 50 mm22 — 14,2;
with a cable cross-section of 70 mm22 — 20,6;
with a cable cross-section of 95 mm22 — 27,9.
Наименования характеристики | Значение |
---|---|
rated operating voltage | 0,66 кВ or 1 кВ |
the frequency of the AC | 50 Hz |
electrical resistance of conducting wires to direct current for 1 km of length at a temperature of 20 °C, om | not more |
with a core cross-section of 16 mm2 | 1,910 |
with a core cross-section of 25 mm2 | 1,200 |
with a core cross-section of 35 mm2 | 0,863 |
with a core cross-section of 50 mm2 | 0,641 |
with a core cross-section of 70 mm2 | 0,443 |
with a core cross-section of 120 mm2 | 0,253 |
with a cable cross section of 25 mm2 | 1,380 |
with a cable cross section of 35 mm2 | 0,986 |
with a cable cross section of 50 mm2 | 0,720 |
with a cable cross section of 70 mm2 | 0,363 |
when the cross section of the phase core is 16 mm2 | 100 |
when the cross section of the phase core is 25 mm2 | 130 |
when the cross section of the phase core is 35 mm2 | 160 |
when the cross section of the phase core is 50 mm2 | 195 |
when the cross section of the phase core is 70 mm2 | 240 |
when the cross section of the phase core is 120 mm2 | 340 |